Permit Number: T21CM09881
Parcel: 137339100

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09881
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09881


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). Now that a Backflow preventer has been added for the Quench Q4 unit The backflow can't be located in the wall. -IPC 608.15, 608.15.2.1 Update Detail B3 on plan page P101 (suggest install in cabinet)
2). SAME-Quench Q4 drain connection saddle fitting not allowed. on plan page P101. -IPC 802.1.3 & 707.1 ( NOTE #6 STILL STATES SADDLE FITTING)
3). Now that an indirect waste connection for Quench Q4 has been shown on Plan Page P101 detail A4 & B4. That indirect connection can't be in a concealed location. -IPC 802.4 ( Suggest move indirect connection to cabinet)