Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09881 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: N/A BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approval Pending 1. Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied Second Review: 1). Now that a Backflow preventer has been added for the Quench Q4 unit The backflow can't be located in the wall. -IPC 608.15, 608.15.2.1 Update Detail B3 on plan page P101 (suggest install in cabinet) 2). SAME-Quench Q4 drain connection saddle fitting not allowed. on plan page P101. -IPC 802.1.3 & 707.1 ( NOTE #6 STILL STATES SADDLE FITTING) 3). Now that an indirect waste connection for Quench Q4 has been shown on Plan Page P101 detail A4 & B4. That indirect connection can't be in a concealed location. -IPC 802.4 ( Suggest move indirect connection to cabinet) |