Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM09881
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 01/10/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09881 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: N/A BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved 1. Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied 1),Water connection for quench q4 on Plan page P101 needs an ASSE 1022 or 1024 backflow device. -IPC 608.17.1 2). Quench Q4 drain connection needs an air gap & saddle fitting not allowed. on plan page P101. -IPC 802.1.3 & 707.1 |
| 01/19/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/20/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/09/2022 | JVINCEN1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |