Permit Number: T21CM09842
Parcel: 11010312A

Address:
3194 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM09842
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2022 LSHAMIS1 ZONING REVIEW Approved
01/12/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/14/2022 JVINCEN1 FIRE REVIEW Approved
01/20/2022 NROSS1 WATER REVIEW Passed
01/20/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09842


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Structural Calculations submitted shows that the Floor Deck is inadequate to support the proposed added loading and need reinforcing. The Architectural Drawings submitted does not show any reinforcing to the Floor Deck. Revise Drawings and resubmit. No Structural Drawing submitted with this submittal.

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approval Pending
E1.1: Cannot read Keynote #1, should correct before issuing for construction.
E6.0: Should call out conductor material for feeders to panels AB and AA-1

PLUMBING REVIEW COMMENTS:
Denied
1). plan Page M1.2 needs to show the condensate drain routing to the termination point for the new equipment. -IPC Section 314

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2022 VVERA1 OUT TO CUSTOMER Completed