Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09836
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. No written response was found that addresses the electrical review comments in this 4th re-submittal. The original electrical comments are not addressed. See comments below. 1. Show the location of all new or relocated electrical equipment, lighting and devices requiring electrical power, show designated branch circuits for power and lighting that correlate with a provided complete panel schedule including load calculations. NEC 408.4. Is the kitchen equipment that is tied in to existing branch circuits new or existing? Is there GFI protection per comment #4? 2. Provide compliance with the 2018 IECC for the lighting. 3. Provide a complete luminaire schedule. 4. Provide GFI protection for all the receptacles located in the kitchen and food prep areas and within 6’ of a sink or within wet areas. NEC 210.8, 210.8B(2). 5. . Provide a legend for all electrical symbols. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |