Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM09836
Parcel: 11522002A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09836
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The proposed metering faucet (Chicago Faucet 404-665ABCP), with a 2.2 GPM aerator outlet, will pass 0.37 gallons in a 10-second cycle. Provide an aerator outlet that will deliver no more than 1.5 GPM in order to pass a maximum of 0.25 gallons in a 10-second cycle. [Second comment: The replacement faucets for the lavatories shall be metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09] [Initial comment: Provide specifications for the new lavatories and faucets in the restrooms. Reference: Sections 303.4 and 402, IPC 2018.]
03/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The previous plan review comment was not addressed. A written response addressing the electrical review comments could not be found in the 3nd submittal as requested. Also provide complete electrical plans designed, and sealed by a registrant registered in the State of Arizona. Provide compliance with all adopted codes.

Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.