Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09836
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The proposed metering faucet (Chicago Faucet 404-665ABCP), with a 2.2 GPM aerator outlet, will pass 0.37 gallons in a 10-second cycle. Provide an aerator outlet that will deliver no more than 1.5 GPM in order to pass a maximum of 0.25 gallons in a 10-second cycle. [Second comment: The replacement faucets for the lavatories shall be metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09] [Initial comment: Provide specifications for the new lavatories and faucets in the restrooms. Reference: Sections 303.4 and 402, IPC 2018.] |
| 03/07/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The previous plan review comment was not addressed. A written response addressing the electrical review comments could not be found in the 3nd submittal as requested. Also provide complete electrical plans designed, and sealed by a registrant registered in the State of Arizona. Provide compliance with all adopted codes. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |