Permit Number: T21CM09836
Parcel: 11522002A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09836
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The replacement faucets for the lavatories shall be metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09 [Initial comment: Provide specifications for the new lavatories and faucets in the restrooms. Reference: Sections 303.4 and 402, IPC 2018.]
02/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The previous plan review comment was not addressed. A written response addressing the electrical review comments could not be found in the 2nd submittal as requested. Also provide complete electrical plans designed, and sealed by a registrant registered in the State of Arizona.

Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.