Permit Number: T21CM09836
Parcel: 11522002A

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM09836
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plumbing plans for new work, relocated fixtures, and relocated appliances. Include water isometrics and waste and vent isometrics as appropriate. Reference: Section 107.2.1, IBC 2018.
2. If new gas-fired appliances have gas pressure or gas demands that are different from the existing appliances, show how the gas piping system can accommodate the new requirements. Reference: Section 402.1, IFGC 2018.
3. The schedule of equipment has numerous item numbers that are noted as spare numbers but are shown on the floor plan (e.g. 26, 28, 29, 32, 33, 34, 35, and 41). Coordinate the floor plan and the equipment schedule. Reference: Section 107.2.1, IBC 2018.
4. Provide specifications for the new lavatories and faucets in the restrooms. Reference: Sections 303.4 and 402, IPC 2018.
01/24/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Show the location of all new or relocated electrical equipment, lighting and devices requiring electrical power, show designated branch circuits for power and lighting that correlate with a provided complete panel schedule including load calculations. NEC 408.4.

2. Provide compliance with the 2018 IECC for the lighting.

3. Provide a complete luminaire schedule.

4. Provide GFI protection for all the receptacles located in the kitchen and food prep areas and within 6’ of a sink or within wet areas. NEC 210.8, 210.8B(2).

5. . Provide a legend for all electrical symbols.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2022 NGARCIA3 OUT TO CUSTOMER Completed