Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM09821
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09821
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09821


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Note: The following items shall be submitted once finalized in next revision as indicated on the response letter by the Architect:
1. Provide Structural Calculations for Foundations and Mezzanine per Section 1601.1 of International Building Code 2018. Provide Structural Calculations for the Building and the Column Reactions for the design of Proposed Footings. Provide Design and Sizes (Length, Width, Depth and Reinforcing) of the Proposed Footings.
2. Provide Wind Load Calculations for the Building per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
5. Areas used for storage are to include 25% of the live load in determining the effective seismic weight. Verify the additional load is applied to the mezzanine lateral resisting system as required in ASCE-7 Section 12.7.2.
6. The mezzanine is supporting equipment loads. Verify the total operating weight of permanent equipment is included in determining the effective seismic weight and applied to the lateral resisting system as required in ASCE-7 Section 12.7.2.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. Air intake openings shall not be located less than 10' horizontally from streets. alleys. parking lots and loading docks (IMC2015,401.1) Not Complied. you did not address the correction, please provide site plan and respond to correction .


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). SAME- Plan set is missing architectural pages, needed for plumbing review completion. -IPC A106.3.1
2). SAME-Plan set is missing Civil & Landscape pages needed for plumbing review completion. -IPC A106.3.1
3-6 OK
7). SAME-Sump pit on P101 needs to be vented. -IPC 712.3.2, Sump pit (basin) shall have gas tight lid & be vented update
Plan Page P103
8). SAME-Add Sump pit detail to Plan page P104. -IPC A106.3.1, 712.3
9-13 OK
14). SAME-Eyewash station on Plan pg. P105 needs ASSE 1071 mixing valve. -IPC 411.3
15-18 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/14/2022 JVINCEN1 FIRE REVIEW Approved
04/15/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
04/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09821
5570 E Travel Plaza Way – C-2
Tire Shop for Semi-Trucks (2nd Review)

TRANSMITTAL: April 15, 2022
This site is located in the C-2 zone (UDC 4.7.21).

1. This comment was not addressed. By definition, see UDC Article 11.3.4.W, the proposed use would be considered Trade Service and Repair: Major, not an allowed use in the C-2 Zone. A rezone of the property to C-3 zone will be required.

2. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
04/21/2022 ROBERT SHERRY WATER REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan (i.e. include the civil utility plans in the building plan set). Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
2. Comment not addressed. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf]
05/19/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comments

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov