Permit Number: T21CM09812
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09812
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The previous electrical plan review comment was not completely addressed. Indicate conduit and conductor sizes and types between the utility transformer and the 200 amp service disconnect switch. This includes from the meter enclosure to the 200 amp service disconnect also.
Ref 2018 IBC sec 107.2.1, 2017 NEC