Permit Number: T21CM09812
Parcel: Unknown

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T21CM09812
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/11/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/20/2022 PETER MCLAUGHLIN ZONING REVIEW Completed
01/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Indicate feeder conduit, conductor sizes and types between the utility transformer and the 200 amp service disconnect switch.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC,
01/20/2022 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Completed
12/27/2021 VFLORES1 COMMUNICATIONS REVIEW Approved
12/30/2021 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2022 VVERA1 OUT TO CUSTOMER Completed