Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM09807
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09807
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The new submittal sheets (New Floor Plan and Interior Wall Detail) must be sealed, signed, and dated by a registered design professional.
01/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a mechanical design performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018.
2. Changes made to drawings sealed by an Arizona Registrant shall be clouded and sealed by the Arizona Registrant making the changes.
01/10/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Designing the site Electrical constitutes the practice of engineering. Provide complete electrical plans including a luminaire schedule that correlates with the lighting and power floor plans, panel schedules, 2018 IECC compliance, tamper resistant receptacles where applicable per NEC 406.12, plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC.
01/10/2022 JGARCIA1 ENGINEERING REVIEW Passed
01/10/2022 JGARCIA1 ZONING REVIEW Passed
01/10/2022 ROBERT SHERRY WATER REVIEW Completed
01/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a plumbing design performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018.
2. Changes made to drawings sealed by an Arizona Registrant shall be clouded and sealed by the Arizona Registrant making the changes.
3. Changes made to the building plumbing shall comply with the Codes and Code amendments currently adopted by the City of Tucson.
4. Provide a plumbing floor plan that shows the location of the two new lavatories. Reference: Section 107.2.1, IBC 2018.
5. The developed length of the hot water supply piping to the new lavatories appears to be greater than allowed by Table C404.5.1, IECC 2018. Show how the hot water supply to the two lavatories will comply with the requirements of Section C404.5, IECC 2018. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.
6. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018
01/10/2022 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/17/2022 GSLEIGH1 FIRE REVIEW Needs Review Fire not reviewed, closed workflow for resub per cust request.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2022 GSLEIGH1 APPROVAL SHELF Completed
02/17/2022 GSLEIGH1 OUT TO CUSTOMER Completed
02/17/2022 GSLEIGH1 REJECT SHELF Completed