Permit Number: T21CM09793
Parcel: 14039052E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM09793
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 JPEELDA1 FIRE REVIEW Approved
01/12/2022 ROBERT SHERRY WATER REVIEW Completed
01/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09793
5300 E Los Reales Rd – PAD-14
Shade structure additions to HHW Facility (1st Review)

TRANSMITTAL DATE: January 12, 2022

This site is located in PAD-14, a land fill and associated accessory use is allowed in the PAD.

1. per UDC Article 3.3.3.G.2.c a new site plan, Development Package (DP), is required to be submitted and approved prior to approval of this building permit. The DP shall meet the requirements of the checklist for Minor Changes to Commercial/Industrial Sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. Zoning was not able to find an approved DP showing the shade structures.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.
01/12/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09793
5300 E Los Reales Rd – PAD-14
Shade structure additions to HHW Facility (1st Review)

TRANSMITTAL DATE: January 12, 2022

This site is located in PAD-14, a land fill and associated accessory use is allowed in the PAD.

1. per UDC Article 3.3.3.G.2.c a new site plan, Development Package (DP), is required to be submitted and approved prior to approval of this building permit. The DP shall meet the requirements of the checklist for Minor Changes to Commercial/Industrial Sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. Zoning was not able to find an approved DP showing the shade structures.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.
01/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09793


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
2. The Structural Calculations state that this submittal is only for the foundations. The Base Plates, Anchor Bolts, Columns, and Canopy Framing is excluded from this submittal. Also the Design of Storage Bunker is excluded from this submittal. Verify and submit response.

BUILDING REVIEW COMMENTS:
Denied
1. The occupant load factor used for the business area is incorrect. Use the correct occupant load factor in accordance with Table 1004.5.

MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). Will OSHA require a eyewash and or emergency shower for this facility? if yes show its location and Plumbing illustrations on plans. -IPC A106.3.1 , IPC 411
2). Does the facility have hose faucets? If yes show its location and Plumbing illustrations on plans. -IPC A106.3.1
3). Show the accessible route with distances to the existing/required restrooms, high/low drinking fountain & service sink. This is mentioned on plan Pg. G0.2 but not illustrated. -IPC A106.3.1 , 403.1, 403.3, 403.5
4). Add gutter/downspout sizes with calculations to plan pg. A1.2 that derive from -IPC 1106.1, 1106.3, 1106.6

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2022 NGARCIA3 OUT TO CUSTOMER Completed