Permit Number: T21CM09755
Parcel: 125073260

Address:
420 N OLSEN AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09755
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Passed
01/03/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/03/2022 ROBERT SHERRY WATER REVIEW Passed
01/19/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The referenced activity T21CM06666 did not include the electrical installation for the water heaters.

“This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by a Registered Electrical Engineer registered in the State of Arizona. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304".

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC,
01/20/2022 STEVE SHIELDS ZONING REVIEW Passed
12/24/2021 SBLOOD1 ENGINEERING REVIEW Approved
12/29/2021 JVINCEN1 FIRE REVIEW Approved