Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM09728
Parcel: 108254810

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09728
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2022 ROBERT SHERRY WATER REVIEW Completed
06/27/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the rim elevation of the next upstream manhole and the first floor elevation of the building. No fixtures located above the rim elevation of the next upstream manhole (e.g. the fixtures on the second floor) may not discharge through the backwater valve. Revise the design of the building drains as needed. Reference: Section 714.1, IPC 2018. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
06/27/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed