Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09727
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/27/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify the rim elevation of the next upstream manhole and the first floor elevation of the building. No fixtures located above the rim elevation of the next upstream manhole (e.g. the fixtures on the second floor) may not discharge through the backwater valve. Revise the design of the building drains as needed. Reference: Section 714.1, IPC 2018. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 06/27/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |