Permit Number: T21CM09677
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM09677
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The previous electrical comments are not addressed. Please comply with the original electrical comment. Provide a written response.

Plans are stamped "For Bid Purposes Only"



1. "This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by a Registered Electrical Engineer registered in the State of Arizona. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304".

Provide electrical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.



Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements,

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2022 VVERA1 OUT TO CUSTOMER Completed