Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09675
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the location of the proposed indirect waste receptor, FS-1, to ensure that it is visible for inspection and has ready access for cleaning. Reference: Section 802.4, IPC 2018. 2. Revise the vent for the floor sink so that it will rise vertically to at least 6" above the flood rim of the floor sink it protects prior to running horizontally. Reference: Section 905.4, IPC 2018. |
| 01/06/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/06/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/13/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 01/13/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/13/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/14/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 12/29/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |