Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM09672
Parcel: 10604072A

Address:
218 E PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09672
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09672


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Note to what appliance these ducts are connecting to on the roof. (IMC2018,106.3.1) Response: Comply. Ducts through roof labeled with the equipment on sheet M2.0. Complied
2. The amount of make up air, shall be approximately the same as the exhaust air. (you are exhausting 5780 cfm’s and bringing in 4600 cfm’s through EC-1 which is interlocked to the exhaust fans 1 and 2) (IMC2018,508.1) Response: Comply. The total make up air provided is 5900 cfm (EC-1: 4600 cfm; AC-1: 400 cfm; AC-2: 400 cfm; AC-3: 500 cfm). Not Complied it shall be noted that the ac1,2 and 3 along with the EC unit (the make up air unit) shall be interlocked with the kitchen exhaust fan on the schedule for the AC units
3. Provide hood for dishwasher (IMC2018,507.5.5). Response: Comply. IMC2018, 507.5.5 Exception: Dishwashing appliances and equipment installed in accordance with Section 507.3. IMC2018 Section 507.3: “Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system.” The dishwasher is a Hobart AM15VL High Temperature Ventless Door-Style Dishewashing Machine. From the manufacturer: “Ventless models AM15VL, AM15VLF, AM15VLT, AM15SVL, and AM15SVLT do not require a vent hood. They use an internal condensing system to minimize the water vapor escaping from the unit during loading and unloading.”. The sensible load and latent load were included in the HVAC system design. Complied
4. The edge of the hood shall extend 6” past the edge of the appliance below (IMC2018,507.4.1). Response: Comply. The hood shown on the food services sheets is incorrect. It should show hoods H1 and H2 with a combined length of 16’-6” which extend 6” past the edge of the appliances. See updated food services sheets for appliance locations Not Complied your sheet FS 6 is all jumbled up, and hard to see clearly what you have, your dimensions are not clearly showing the length of the hood on that sheet please make clear
5. Explain what this hood is for, it is not on the mechanical plans, and you got 2 island hoods that are 8’3” each, side by side on M4.2. This hood is 15’11” long it is different than the hoods on sheet M4.2 (IMC2018,106.3.1)Response: Comply. The food service drawings did not have the latest hood drawings. The food service sheets will be updated with the correct hood drawings. Not Complied will need the revised plans with the manufacturers specs and the cooking appliances it serves you have not provided any of this information for this hood need the revised plans.

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). OK- . The New restroom on Plan pages P1.1 & A1.0 can't open directly into the kitchen area -IPC 403.3.2 (PLAN PAGE A1.0 HAS BEEN UPDATED)
2). SAME-Due to the quantity & type of items required to connect to the grease system in this establishment a hydromechanical grease interceptor can't be used. Update plan pages P1.1 & P3.0. with a gravity type grease interceptor - Tucson Amendment IPC 1003.3 See Tuscon amendment below.
Hydromechanical grease interceptors. Hydromechanical grease interceptors (HGI), which are generally installed inside, may be used when there are four (4) or fewer fixtures. The minimum size HGI to be installed shall be rated no smaller than 25 gallon per minute with a 50 pound grease capacity. Flow Control devices shall be designed and installed so that the total flow through such devices shall at no time be greater than the rated flow.
Exception: If a dishwasher or food waste disposal unit is used in the facility, an HGI (hydromechanical)cannot be used and an appropriately sized GGI (Gravity Grease Interceptor) or alternative pretreatment device, capable of accepting these wastes, must be installed.
3). SAME-The K4 ice machine & rooftop condensate can't discharge to the grease system, Update P1.1 & P1.3 -IPC 1003.2
4). SAME PENDING SOLUTION TO COMMENT #2- . Add Grease interceptor sizing calculations to plan pg. P3.0 -IPC 1003.3.7
5). OK
6). SAME-Rooftop water connections to evaporator coolers on plan Pg. P1.1 need backflow protection. -IPC 608.3 ( EC-1 specs sheets don't show internal air gap) notate air gap or backflow on required on plan page P1.1
7). SAME- Add note to plan pg. P3.0 stating any beverage equipment connected to the water system will need to comply with - IPC 608.17.1 (NOTE NOT ADDED AS STATED ON RESPONSE SHEET)
8). OK
03/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09672
218 E Prince Rd – C-2
Remodel existing Kitchen w/expansion (2nd Review)

TRANSMITTAL: March 9, 2022
This site is located in the C-2 zone (UDC 4.7.21).

1. Until DP21-0304’s revision is approved the building plans cannot be approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/18/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov