Permit Number: T21CM09672
Parcel: 10604072A

Address:
218 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09672
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 JPEELDA1 FIRE REVIEW Approved
01/11/2022 ROBERT SHERRY WATER REVIEW Completed
01/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/12/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning Comments
01/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09672


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Multiple new RTU’s are placed on existing roof. Provide structural calculations justifying the adequacy of existing roof joists to support additional loading from the new RTU’s.
2. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.

BUILDING REVIEW COMMENTS:
Denied
1. Provide occupant load calculation for the renovated space.
2. Provide a thorough egress plan,.
3. There are various typos on the cover sheet regarding construction type, etc.

MECHANICAL REVIEW COMMENTS:
Denied
1. Note to what appliance, these ducts are connecting to on the roof (IMC2018,106.3.1)
2. The amount of make up air, shall be approximately the same as exhaust air. (you are exhausting 5780 cfm's and bringing in 4600 cfm's through EC-1 which is interlocked to the exhaust fans 1 and 2) (IMC2018,508.1)
3. Provide hood for dishwasher (IMC2018,507.5.5)
4. The edge of the hood shall extend 6" past the the edge of the appliance below (IMC2018,507.4.1)
5.Explain what this hood is for, it is not on the mechanical plans, and you got 2 island hoods that are 8'3" each, side by side on M4.2. this hood is 15' 11" long it is different than the hoods on sheet M4.2 (IMC2018,106.3.1)

ELECTRICAL REVIEW COMMENTS
Denied
e4.1 electrical panel schedules and single line diagram:
Panel B’s 200 amp CB is mismatched to the #1 conductor feeding into Panel B2.
What is the estimated load on Panel B2?

PLUMBING REVIEW COMMENTS:
Denied
1). The New restroom on Plan pages P1.1 & A1.0 can't open directly into the kitchen area -IPC 403.3.2
2). Due to the quantity & type of items required to connect to the grease system in this establishment a hydromechanical grease interceptor can't be used. Update plan pages P1.1 & P3.0. with a gravity type grease interceptor -Tucson Amendment IPC 1003.3
3). The K4 ice machine & rooftop condensate can't discharge to the grease system, Update P1.1 & P1.3 -IPC 1003.2
4). Add Grease interceptor sizing calculations to plan pg. P3.0 -IPC 1003.3.7
5). Sanitary & Grease riser on P2.0 doesn't illustrate any vents to open air -IPC 904.1
6). Rooftop water connections to condensing units on plan Pg. P1.1 need backflow protection. -IPC 608.3
7). Add note to plan pg. P3.0 stating any beverage equipment connected to the water system will need to comply with - IPC 608.17.1
8). Add gas sizing table used to plan pg. P1.2 or P1.3. IFGC 402.4
01/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09672
218 E Prince Rd – C-2
Remodel existing Kitchen w/expansion (1st Review)

TRANSMITTAL: January 12, 2022
This site is located in the C-2 zone (UDC 4.7.21).

1. Per UDC Article 3.3.3.G.2.c as you are proposing a building expansion, a site plan, development package (DP), meeting the requirements of Administrative Manual 2-06 shall be submitted and approved prior to approval of this permit. Currently there is an open DP, DP21-0304, that could be revised or if a new DP is requested DP21-0304 will need to be closed.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.