Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09666

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1).OK
2). SAME- Add 1" hot water pipe insulation to plan page P0.01 -IPC 607.2.1 607.5 (Spec manual not sent)
3). SAME-add seismic supports to WH detail on plan page P7.01 -IPC 502.4 (PLBG General Notes #5 & #7 on P0.02 states
plumbing supports to be shown & installed...... All equipment in drawings shall comply with state/Local codes
03/09/2022 STEVE SHIELDS ZONING REVIEW Approved
03/17/2022 SBLOOD1 ENGINEERING REVIEW Passed