Permit Number: T21CM09634
Parcel: 13414012D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09634
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 JGARCIA1 ZONING REVIEW Passed
01/05/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change This apartment requires 45 CFM of continuous ventilation. Show how this is being accomplished. Reference: Section R403.6, IECC 2018.
01/05/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/05/2022 JGARCIA1 ENGINEERING REVIEW Passed
01/05/2022 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/05/2022 ROBERT SHERRY WATER REVIEW Completed
01/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. The disconnect switch and equipment shown in bedroom #2 is assigned to branch circuit #A:30. The new panel ‘A’ is limited to 24 circuits. Please clarify.

2. Provide for a lighting outlet in the bathroom #2 tub area. NEC 210.70

3. The description of the scope of work on the title sheet included replacing the luminaires (light fixtures). Provide compliance with the 2018 IECC residential section. Also the replaced exterior luminaire lamp color temperature output must not exceed 3500k. Section 402.1 OLC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code, (OLC).
01/14/2022 JVINCEN1 FIRE REVIEW Approved
12/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved