Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T21CM09600
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/03/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 01/10/2022 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
| 01/10/2022 | PETER MCLAUGHLIN | ZONING | REVIEW | Completed | |
| 01/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Indicate conduit, conductor sizes and types between the electrical service meter and the service main disconnect switch, AIC rating and fuse type. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, |
| 12/15/2021 | PCAMARE1 | COMMUNICATIONS | REVIEW | Completed | |
| 12/29/2021 | JVINCEN1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |