Permit Number: T21CM09559
Parcel: Unknown

Address:
1265 W ROGER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09559
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09559
1265 W Roger Rd – R-3
Add four (4) additional units to site. (1st Review)

TRANSMITTAL: January 6, 2022
This site is located in the R-5 zone (UDC 4.7.12). A Multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

1. UDC Article 3.3.3.G.2.c as you are proposing a change of use for a portion of the building a development package (DP) is required. This DP shall meet the requirements of the checklist for Minor Changes to a Commercial/Industrial Site found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using submission type “Site Review”. This DP must be submitted and approved prior to approval of the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
01/06/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/06/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
01/06/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09559

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied

1. Provide an existing floor plan along with a demolition plan.
2. Provide a Building Code Data Legend on the Title Sheet. Include the following code information for each building proposed:
• Occupancy Classification(s)
• For Mixed Occupancy Buildings, state whether the “non-separated” or “separated” option was chosen from Sections 508.3 / 508.4.
• Description of Use
• Type of Construction
• Sprinklers:
• Stories
• Height
• Floor Area
• Occupant Load

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
01/06/2022 ROBERT SHERRY WATER REVIEW Completed
02/09/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments

john.vincent@tucsonaz.gov
520-349-5581
12/14/2021 LBOWERS1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE CONTACT PC ADDRESSING TO HAVE UNIT NUMBERS ASSIGNED TO THE NEW UNITS. PLEASE SUBMIT CONFIRMATION FROM PC ADDRESSING WHEN RESPONDING TO COMMENTS IN ORDER TO CLEAR THIS ISSUE.

ADDRESSING CAN BE CONTACTED AT 520-724-9512 OR ADDRESSING@PIMA.GOV