Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09559
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM09559 1265 W Roger Rd – R-3 Add four (4) additional units to site. (1st Review) TRANSMITTAL: January 6, 2022 This site is located in the R-5 zone (UDC 4.7.12). A Multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6. 1. UDC Article 3.3.3.G.2.c as you are proposing a change of use for a portion of the building a development package (DP) is required. This DP shall meet the requirements of the checklist for Minor Changes to a Commercial/Industrial Site found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using submission type “Site Review”. This DP must be submitted and approved prior to approval of the building plans. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
| 01/06/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/06/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 01/06/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09559 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. Provide an existing floor plan along with a demolition plan. 2. Provide a Building Code Data Legend on the Title Sheet. Include the following code information for each building proposed: • Occupancy Classification(s) • For Mixed Occupancy Buildings, state whether the “non-separated” or “separated” option was chosen from Sections 508.3 / 508.4. • Description of Use • Type of Construction • Sprinklers: • Stories • Height • Floor Area • Occupant Load MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved |
| 01/06/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/09/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | See building comments john.vincent@tucsonaz.gov 520-349-5581 |
| 12/14/2021 | LBOWERS1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | PLEASE CONTACT PC ADDRESSING TO HAVE UNIT NUMBERS ASSIGNED TO THE NEW UNITS. PLEASE SUBMIT CONFIRMATION FROM PC ADDRESSING WHEN RESPONDING TO COMMENTS IN ORDER TO CLEAR THIS ISSUE. ADDRESSING CAN BE CONTACTED AT 520-724-9512 OR ADDRESSING@PIMA.GOV |