Permit Number: T21CM09555
Parcel: 10714376G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 IMONSHI1 ZONING REVIEW Approved
01/04/2022 IMONSHI1 ENGINEERING REVIEW Passed
01/04/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/05/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Specify the air flow rate for the new restroom exhaust fans. Ventilation for restrooms in public spaces requires a minimum of 50 CFM of mechanical exhaust per water closet or urinal if the exhaust is continuous and 70 CFM if the exhaust is intermittent. Reference: footnote e, Table 403.3.1.1, IMC 2018.
01/05/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018.
2. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
3. The specified safety eyewash is a self-contained unit with a 7-gallon water storage tank and has no provision for a piped water connection. Why is water being piped to the unit? Reference: Section 107.2.1, IBC 2018.
01/05/2022 ROBERT SHERRY WATER REVIEW Completed
01/11/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/14/2022 JVINCEN1 FIRE REVIEW Approved
12/21/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved