Permit Number: T21CM09544
Parcel: 116300240

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM09544
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide an engineer stamped plan showing the location of each alteration.

Update the post detail showing the connection of the new wood post to an existing beam.

Provide a special inspection request form for inspector approval of the private epoxy installation inspector, R109.2.
For certified inspectors see:
https://www.orovalleyaz.gov/Government/Departments/Community-and-Economic-Development/Special-Inspections
12/15/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/28/2021 IMONSHI1 ZONING REVIEW Passed