Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09536
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/04/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/04/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/04/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 01/04/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/04/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/11/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/14/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | See building comments |
| 12/20/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1; Code Study: The shell space requires a separate permit for any work (demolition/construction) that is outside of the new office space. Please remove information in the Code Study that includes the Shell Space (Area, Occupant Load, General Building Summary, Exits Required, Plumbing Fixtures). That information should be included in a future tenant improvement. 2. Sheet D1; Demolition Floor Plan: Remove any demolition and demolition notes that occur outside the Suite D6 area. 3. General: Please provide written responses to all review comments. |