Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The sealed, signed, and dated drawing indicates this is "Preliminary Only. Final Design to Follow". Please provide a site plan with the building indicated on that plan, and show the number and dimensioned placement of all helical piers. That drawing must be sealed, signed, and dated, but can not be preliminary only.
2. General: Please provide structural calculations/tables as required verifying the number and size of helical piers required.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2022 VVERA1 OUT TO CUSTOMER Completed