Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/31/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/01/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS.1; Project Code Check: Although the Occupancy Classification for this project per the IBC Section 304 is Business (B), the Maximum Floor Area Per Occupant, using the IBC Table 1004.5, should be 50 (Exercise Rooms). The Occupant Load calculation would be 4825/50 = 97 total occupants (49 males and 48 females). Using the IBC Table 2902.1 for Assembly (Gymnasiums), water closets for males are 1 per 125, and females are 1 per 65. Lavatories for males and females are 1 per 200. These calculations would require one male and one female water closet and one male and one female lavatory. Please revise the Project Code Check. |