Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM09519
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/05/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
01/06/2022 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
01/06/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
01/24/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
12/22/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide structural calculations to verify the existing roof structure can adequately support the new loads from the PV system. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/24/2022 | VVERA1 | OUT TO CUSTOMER | Completed |