Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM09517
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Based on DP20-0045, backwater valves are required for buildings 47, 48, 50, 51, 83, 84, and 85 in addition to buildings 95, 96, and 97 that are noted on the current plans. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson. 2. The use of saddle-type fittings to connect to a private sewer is prohibited. Use directional fittings as noted in Detail RWRD 401. Reference: Section 707.1 (6), IPC 2018. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/11/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |