Permit Number: T21CM09517
Parcel: 13213066A

Address:
2805 S PARK AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM09517
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Based on DP20-0045, backwater valves are required for buildings 47, 48, 50, 51, 83, 84, and 85 in addition to buildings 95, 96, and 97 that are noted on the current plans. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
2. The use of saddle-type fittings to connect to a private sewer is prohibited. Use directional fittings as noted in Detail RWRD 401. Reference: Section 707.1 (6), IPC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2022 NGARCIA3 OUT TO CUSTOMER Completed