Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T21CM09481
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM09481 902 W Irvington Rd – C-2 Automotive – Service and Repair - Minor (1st Review) TRANSMITTAL: January 4, 2022 This site is located in the C-2 zone (UDC 4.7.21). Automotive – Service and Repair - Minor is a permitted use in the zone, (UDC TABLE 4.8-4) subject to Use Specific Standard 4.9.13.E. 1. As the first review of DP21-0344 has not been completed Zoning will review the building plans on the next submittal for compliance with the DP. Zoning cannot approve the building plans until the DP is approved. 2. Clarify why the building plans were submitted under 902 W Irvington Rd which is an addressed not associated with this parcel and DP21-0344 was submitted under 850 W Irvington which is an address associated with this parcel. A new application with the correct addressed should be submitted with the next building plan submittal. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 01/04/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/10/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the site plan referenced on sheet P1.01 showing the location of the water meter, reduced pressure backflow assembly and the route of the water service to the building. Specify the material of construction for the water service pipe. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Reference: Section 107.2.1, IBC 2018. |
| 02/02/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | The DP needs to be approved before the building plans can be approved. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 02/09/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | See building comments john.vincent@tucsonaz.gov 520-349-5581 |
| 12/17/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09481 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. The occupancy class provided is incorrect. Auto repair garages are classified as an S-1 occupancy in accordance with Section 311.2. 2. Provide the occupant load calculation. Simply stating the occupant load is not sufficient. Provide the areas along with the occupant load factors from Table 1004.5. 3. Provide a detail of the alternating tread device that complies with applicable requirements of Section 1011.14. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS Denied 1. Provide supply and waste isometrics. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2022 | VVERA1 | OUT TO CUSTOMER | Completed |