12/13/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM09458
512 N SHAWNEE AV


TRANSMITTAL DATE: December 13, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Based on a demand of 235,000 the mainline must be a 1-inch pipe. The 3/4" pipe is only good for 170,000 demand for the developed length of 31ft. On the template, there are four appliances checked but on the line diagram, there are only three appliances shown. Clarify if there are four or three appliances. The furnace is undersized, at a developed length of 31 with a demand of 100,000 a 1/2" pipe will only provide 81,000 please change to a 3/4" which will provide 170,000.


COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans