Permit Number: T21CM09404
Parcel: 10824086A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09404
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/04/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/04/2022 ROBERT SHERRY WATER REVIEW Completed
01/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan sheet G0.00 ‘PROJECT DATA NOTES’ #3. Could not locate plan sheet E6.10 in the plan set. Please clarify.

Please address wiring methods with a note requiring compliance with NEC 517.13.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code.
02/01/2022 JPEELDA1 FIRE REVIEW Reqs Change IFC 2018, Section 5306.2.2 One-hour interior room. Provide documentation showing that the interior medgas room meets the mechanical ventilation requirements.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
12/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/31/2021 STEVE SHIELDS ZONING REVIEW Approved
12/31/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed