Permit Number: T21CM09366
Parcel: 134181060

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM09366
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show the New Patio on the site plan.

Remove the AFCI exception from sheet #12 as this is not part of E3908.8.
12/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/17/2021 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T21CM09366
7402 E Placita Mono
Addition to existing house (1st Review)

TRANSMITTAL DATE: December 17, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5-.9.

1. COMMENT: The existing porte-cochere and the existing garage appear to have been constructed between 2005 and 2008 without issuance of permits. Please provide permit documentation of these structures. If permits were not issued, please include the porte-cochere and the garage within the current scope of work.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at (520)837-4951.