Permit Number: T21CM09362
Parcel: 12801007A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09362
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/14/2022 JVINCEN1 FIRE REVIEW Approved
12/09/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/15/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a site plan and a building plan indicating the location of the new HVAC units.
2. General: Please indicate the weight of the old units on the building plan drawing and the weight of the new units. Verify if a structural analysis is required for the existing roof structure to support the new units.
12/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.
12/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/28/2021 ROBERT SHERRY WATER REVIEW Passed
12/29/2021 STEVE SHIELDS ZONING REVIEW Passed
12/29/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed