Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM09311
Parcel: 132191230

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09311
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Second comment: Revise the waste and vent isometric to show a vent configuration that is described in Chapter 9, IPC 2018 and indicate on the isometric how the fixture drain connects to a building drain. Reference": Section 901.2.1, IPC 2018 and Section 107.2.1, IBC 2018.] [Initial comment: Provide a direct connection for the new floral sink, PL1F. Plumbing fixtures that receive or discharge liquid waste shall be directly connected to the sanitary drainage system. Reference: Section 301.3, IPC 2018.]
02/10/2022 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2022 DBENOIT1 APPROVAL SHELF Completed
02/10/2022 DBENOIT1 OUT TO CUSTOMER Completed
02/10/2022 DBENOIT1 REJECT SHELF Completed