Permit Number: T21CM09299
Parcel: Unknown

Address:
4806 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09299
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

6. Description of Work - Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit.

7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

8. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

9. Supporting Documentation Upload - Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful.

10. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/09/2022 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/08/2021 JPEELDA1 FIRE REVIEW Approved
12/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
12/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/20/2021 ROBERT SHERRY WATER REVIEW Passed
12/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Electrical line diagram.

1 . Indicate AIC ratings of the service equipment, also show the conduit, conductor sizes and types for the electrical service secondary feeders.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements
12/27/2021 LSHAMIS1 ZONING REVIEW Passed