Permit Number: T21CM09269
Parcel: 138170410

Address:
414 E ELVADO RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM09269
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 ROBERT SHERRY WATER REVIEW Completed
01/10/2022 JPEELDA1 FIRE REVIEW Approved
02/01/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

6. Description of Work - Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit.

7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

8. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

9. Supporting Documentation Upload - Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful.

10. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
12/15/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09269

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
2. Submit documentation regarding implementation of Special Inspections and Testing program during construction to observe compliance with the Design Concepts and Specifications.
3. Provide schedule of special inspections as required in IBC Section 1705.
4. Provide concrete data on the drawings for footings, walls, exterior slab, interior slab, beams and columns. F’c max, Max W/C ratio, Max aggregate size, Slump, Entrained Air Percent (+/- 1.5%), Cement Type.
5. Non-load bearing walls require a deflection track or details to allow for the relative lateral deflection of the structural members.
6. The Structural Calculations submitted references ASCE7-10. Revise Calculations per ASCE7-16.
7. DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official..
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. An occupant notification system is required per Section 907.2.1 and Section 907.5.
2. Provide a thorough egress plan that shows compliance with all of the applicable requirements of Chapter 10. This includes travel distances and separations of exits along with all other requirements.
3. Provide a complete schedule of special inspections along with the statement of special inspections.


MECHANICAL REVIEW COMMENTS:
Conditionaly Approved
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E-1: Note 9 might be interchanged with Note 4 on drawing.


PLUMBING REVIEW COMMENTS:
Denied
1). add code summary to plan page G-1. -IPC 106.3.1
2). add gutter & downspout sizing & calculations that derive from IPC 1106.6 & 1106.3 to plan page. A-10
3). Flat roof on plan pg. A-10 only shows primary scuppers, secondary drainage is required. -IPC 1106.5 & 1108
4). Need primary & secondary scupper sizing calculations added to plan pg. A-10 -IPC 1106.5 & 1108.3
5). Plans need to be accompanied by the site utility piping plan for continuation sewer, water service, & storm sewer. -IPC A106.3.1
6). Put a sign above 1 compartment sink & handsink in drinks/serving room that states "no food prep or dishwashing". Per Tucson Plumbing code amendment 1003.3 update plan pg. P-6 fixture schedule with notation.
7). The Schirer GB75 grease interceptor selected is an Hydromechanical type, per Tucson Plumbing code amendment 1003.3 this type can only be used for 4 fixtures or less. ( suggest 1 concrete gravity type, or multiple hydromechanical)
8). Condensate on plan page P-3 can't discharge to grease system, -IPC 1003.3.1
9). Plan P-6 grease interceptor sizing calculations are stating a 100 GPM unit is required for a 2 minute rating. A 75 GPM unit was selected. update page information -IPC 1003.3.5 ( this comment is also affected by comment #7)
10). Condensate detail 217 on plan pg. P5.1 & plan pg. P2, can't route condensate to lavatory waste direct connection. (suggest show floor sink in Mechanical closet) -IPC 802.1.5
11). Mixing valve on plan page P5 detail # 204 needs to be an ASSE 1070 type. -IPC 419.5
12). Hose bibs need shut off valves. Update all plumbing pages. -IPC 606.2
12/24/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09269
348 E Elvado Rd – O-3
New Religious Use Bldg (1st Review)

TRANSMITTAL: December 24, 2021

This site is located in the O-3 zone (UDC 4.7.15). Religious Use is a permitted use in the zone, (UDC TABLE 4.8-3) subject to Use Specific Standard 4.9.13.K.

1. Zoning has reviewed the building plans for compliance with DP20-0172. The building plans show a proposed canopy that was not shown on the DP. A revision to the DP showing the proposed canopy will need to be submitted and approved prior to approval of this building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
12/24/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2022 VVERA1 OUT TO CUSTOMER Completed