Permit Number: T21CM09255
Parcel: 108240950

Address:
2472 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM09255
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 SBLOOD1 ENGINEERING REVIEW Passed
12/07/2021 JPEELDA1 FIRE REVIEW Approved
12/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the dimensions of the roof scuppers. Reference: Section 1106.5, IPC 2018.
2. Provide secondary (overflow) roof drainage. Note that the "overflow cutout" does not qualify as a secondary (overflow) scupper. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
12/14/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the energy code compliance for the building envelope and the mechanical systems to show the structure is new construction, not an addition to an existing building. Note that the interior lighting has been designed to comply with Section C406.3, IECC 2018 so no further "Additional Efficiency Package Option" will be required. Reference: Sections C202, International Energy Conservation Code 2018.
2. The R and U value note on sheet TS1 calls for R-38 roof cavity insulation and R-21 wall cavity insulation. The COMcheck envelope compliance components show R-38 roof cavity insulation but no wall insulation. The drawings, however, show no insulation for either the roof or the walls.
3. Include the three windows and four skylights as envelope components and revise the entry door to comply with the fenestration requirements as a non-opaque door. Reference: Section C402.4, IECC 2018.
12/14/2021 ROBERT SHERRY WATER REVIEW Passed
12/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/24/2021 STEVE SHIELDS ZONING REVIEW Approved
12/24/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2022 NGARCIA3 OUT TO CUSTOMER Completed