Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM09246
Parcel: 140232630

Address:
6009 S EUCLID AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM09246
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show compliance with R310 providing egress from bedrooms with minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor). Also, show the minimum net clear opening dimension of 24" height and 20" width, and maximum sill height of 44".

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

Provide heating facilities in all habitable rooms, R303.9.
Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
12/08/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/13/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM09246
Residential Addition
December 17, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. On the elevation drawings, please measure the building height from design grade. Please add measurements of the height at the lowest, highest, and midpoint of the pitched roof.
2. Please make a note that the detached accessory structure in the southeast corner of the lot is no longer present.
3. Add any vehicle use area (including driveway) to the lot coverage and recalculate to reflect the added square footage.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov