Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM09225
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM09225
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/14/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The "outdoor air provided" schedule calls for 500 CFM of outside air for each of the three 5-ton AC units but shows a total of 888 CFM of outside air. If you plan to provide 1500 CFM of outside air using the existing AC units, show how the control system will be able to reduce the outdoor air supply to the required 888 CFM of ventilation. Reference: Section C403.2.2, IECC 2018. [Initial comment: Clarify the calculations shown in the "outdoor ventilation air provided" schedule.]
2. The revised exhaust schedule now shows the correct number of water closets but the "total exhaust supplied" and the "total air supplied" columns for one restroom still show 225 CFM for both exhaust and supply air.
02/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/14/2022 ROBERT SHERRY WATER REVIEW Completed
02/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/08/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/08/2022 LSHAMIS1 ZONING REVIEW Reqs Change Zoning acknowledges an associated Development Package (DP) has been submitted however, Zoning cannot approve this building permit until the DP has been approved for Zoning, and these plans have been reviewed against the DP.
03/10/2022 JPEELDA1 FIRE REVIEW Reqs Change Code REview & Applicable Codes Sheet CVR:
Fire Prevention Code amandments shall say Yes
Plans shall show that the fire alarm is deffered and shall be submitted to TFD
Note shall be added that the owner shall obtain a State Licnesed Facility permit from TFD

Questions:
Jennifer Peel-Davis
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov