Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09225
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet CVR; Code Review: This sheet indicates an allowable area of 6000 SF. Please revise per the IBC Table 506.2 (and your sheet A-1.0). 2. Sheet CVR; Code Review: This sheet indicates an occupant load of 92 occupants, or 75 children. Sheet A-1.0 indicates 79 occupants. Please coordinate the total occupant load to be listed on the C of O. 3. Sheet CVR; Code Review: This sheet indicates one exit is required, while Sheet A-1.0 indicates two exits required. Please coordinate. 4. Sheet CVR (Code Review); Sheet A-1.0 (Code Analysis): On one of these sheets, please indicate the plumbing requirements including water closets, lavatories, drinking fountains, and service sinks. Verify on this drawings those requirements are met. 5. Sheet CVR (Code Review); Sheet A-1.0 (Code Analysis): The Occupancy Classification is listed as E on these sheets. Since the E Classification indicates that it is for children older than 2 1/2 years of age, the Occupancy Classification I-4 (IBC Section 308.5) would be a better Classification. Please verify and revise the drawings as required. 6. Sheet A-1.0; Demolition Plan: Please provide the notes indicated on the Demo Plan. 7. Sheet A-1.2; Handicap Restroom Dimensions: Please provide the distance of the vertical grab bar to the rear wall per the ICC/ANSI Figure 609.4.2. 8. Sheet A-1.2; Handicap Restroom Dimensions: All grab bar dimensions should follow ICC/ANSI Figure 609.4.2 for children's use. 9. General: Please provide written responses to all review comments. |
| 12/06/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Occupan load factor used on cover sheet is 35 net but ib A-1.0 25 is used in some areas. These areas might qualify as a classroom but then it would be 20 net not 25. Please adjust your occupant load and factors Reception/kitchen and laundry shall be shown in the occupant load as well. Plans shall show that the fire alarm is deffered and shall be submitted to TFD Questions: Jennifer Peel-Davis 520-837-7033 Jennifer.Peel-Davis@Tucsonaz.gov |
| 12/10/2021 | WBERGER1 | ZONING | REVIEW | Reqs Change | RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please resubmit updated drawings along with a detailed comment response letter, which states how all zoning review comments were addressed. 1. COMMENT: Any site improvements and/or expansion of use area must be approved first on a Development Package. Zoning cannot approve until a Development Package has been approved. 2. COMMENT: Please refer to the Use-specific Standards that apply to Day Care facilities in the R-1 and C-1 zones (UDC Table 4.8-2 and Table 4.8-4). 3. COMMENT: A Day Care use with more than 30 children in the R-1 zone requires a Zoning Examiner Special Exception Procedure (UDC 3.4.3). If you have any questions about this transmittal, contact Wyatt Berger (520)837-4951 or at Wyatt.Berger@tucsonaz.gov. |
| 12/10/2021 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 12/10/2021 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Reqs Change | |
| 12/16/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the balancing data for HP2 and HP-3 shown on the plans is coordinated with the mechanical unit schedule. Reference: Section 107.2.1, IBC 2018. 2. Coordinate the number of water closets in each restroom in the exhaust/make-up air requirements schedule with the number of water closets shown in each restroom in the mechanical plan. Reference: Section 107.2.1, IBC 2018. 3. The restroom exhaust fan symbol calls for 75 CFM of exhaust. Coordinate the exhaust fan flow rates shown on the mechanical plan with the exhaust/make-up air requirements schedule. Provide a minimum exhaust flow rate of 50 CFM per water closet or urinal if the exhaust is continuous, 70 CFM if the exhaust is intermittent. Reference: Section 107.2.1, IBC 2018, and Section 403.3.1.1 and Table 403.3.1.1, IMC 2018. 4. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018. 5. Clarify the calculations shown in the "outdoor ventilation air provided" schedule. 6. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018. |
| 12/16/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show all of the pipe sizes on the waste and vent isometrics. Reference: Section 107.2.1, IBC 2018 2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. 3. Provide the water pressure and pipe sizing calculations; verify that sufficient water pressure is available. The notes shown on P-2.0 state that the distance to the furthest fixture is 96-feet, the available pressure is 40-49 PSI, and a 2" water line is provided but the water meter appears to be over 450-feet away from the suite and the 2" water line is not shown. Reference: Sections 604.3 and 604.7, IPC 2018. 4. Verify that the lavatory faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 5. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. 6. Show how the temperature of the tempered water supply to the public lavatories is controlled. Reference: Sections 416.5 and 607.1.2, IPC 2018 and Section C404.3, IECC 2018. 7. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 8. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.1.7, IPC 2018 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.1.1 and 708.1.8, IPC 2018. 9. Determine the size of the wastewater pipes using the fixture units shown in Table 709.1. Reference: Section 710, IPC 2018. |
| 12/16/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018. |
| 12/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. 2. Provide for tamper resistant receptacles where applicable per NEC 406.12. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code. |