Permit Number: T21CM09221
Parcel: 14042072B

Address:
7060 S TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09221
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09221


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved
1. On almost every page of the drawing set, the file seems corrupted and there are lines running through the floor plan.
2. On almost every page of the drawing set, lines are missing from the drawing. Please correct drawing and provide a completed drawing.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide mechanical plans (IMC2018,106.3.1) Not Complied


ELECTRICAL REVIEW COMMENTS
Denied
No electrical design provided as per Sheet 001, General Notes-Project; Item B4
This note states that an Electrical design will be provided by the Electrical contractor.
Until such design is submitted, the electrical permit cannot be approved.
Electrical permit application: Denied.


PLUMBING REVIEW COMMENTS:
Denied
1). OK
2). Response to comment 1 states see General notes B-4 on Plan page 001. Are these notes insinuating that there is more plumbing work than just the fixture replacements being shown on the current plans that is being permitted separately? is that permissible by the jurisdiction? -IPC A106.3.1
01/24/2022 SAMUEL ROGERS ZONING REVIEW Approved