Permit Number: T21CM09202
Parcel: 119421830

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM09202
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/07/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The supply and waste plumbing for the clothes washer/dryer is not shown.[Initial comment: Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Show how the new plumbing fixtures (including the washer/dryer identified on sheet E1.0) connect to the existing plumbing systems. Reference: Section 107.2.1, IBC 2018.]
2. The drain for a water heater pan may not discharge to a p-trap; it must terminate at an indirect waste receptor or the exterior of the building. [Initial comment: Show the location where the drain from the water heater pan terminates. The drain from a pan located under a water heater shall terminate either to an indirect waste receptor or to the exterior of the building. The tailpiece of a fixture is not an approved indirect waste receptor. Reference: Sections 504.7.2 and 802.4, IPC 2018.]
02/07/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved