Permit Number: T21CM09093
Parcel: 13711425B

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM09093
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . DP plans are not to be used for construction purposes. 2.Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Provide a complete line diagram. Include; (A) AIC ratings and secondary conduit, conductor sizes and types on the line diagram. (B) Complete panel schedule, voltage, phase, amp and AIC ratings, all OPCD’s ratings, main breaker or main lug only , load calculations. (C) Locate the 200 amp service and sub- panel on the site plan.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2021 NGARCIA3 OUT TO CUSTOMER Completed