Permit Number: T21CM09063
Parcel: 13214024E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM09063
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2021 JPEELDA1 FIRE REVIEW Approved
12/10/2021 ARUIZ1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Completed Building numbers have never been assigned by Pima County Addressing 520-724-9623. Please contact them to provide accurate Building numbers to add to your permit numbers and CofO before issuance.
12/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The current submitted set of documents have the architect's seal that is sealed, signed, and dated in 2008. Please update.
2. General: It is not clear if the R-2 Occupancy Classification is for a hotel (non-transient) or apartments. Please clarify.
3. General: Since there are no kitchens, this permit would appear to be a non-transient hotel (sleeping units). If it is meant to be an apartment (dwelling units), then a kitchen is required per the IBC Table 2902.1. Please verify.
4. General: If this is meant to be apartments (dwelling units), then cooking facilities are required per the IBC Section 202 definitions. Please clarify.
5. General: Please verify the walls separating dwelling units (apartments) or sleeping units (non-transient hotel) meet the requirements of the IBC Sections 420.2 and 708.3 for fire separation.
6. General: Please provide written responses to all review comments.
12/14/2021 LOREN MAKUS ENGINEERING REVIEW Passed
12/20/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM09063 & T21CM09064
810 E Benson Hw – C-2
Convert Motel to Multi-Family

TRANSMITTAL: December 20, 2021

This site is located in the C-2 zone (UDC 4.7.21). Multi-Family is an allowed use in the zone (UDC Table 4.8-4).

1. Per UDC Article 3.3.3.G.2.c a site plan is required for existing development undergoing a change of use, building or structure additions, and/or a reconfiguration of an area outside a building. Based on the site plan provided in this building set and approved DP21-0243 there are proposed changes to the site, i.e. removal of vehicle parking spaces to allow for a grassed play area along the north side of the parcel.

2. Based on current aerial photos there is metal fencing and gates near the northeast and northwest corners of Building 1 that are not show on the plan. Clarify if the fence & gates are to remain. If they are to remain a revision to DP21-02243 will be required.

3. It appears that some of the units could have two (2) bedrooms as called out as “DOUBLE” on the plan. If these are proposed to be two (2) bedroom units the vehicle parking space calculation will need to be revised.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2021 NGARCIA3 OUT TO CUSTOMER Completed