The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM09060
Parcel: 110121080

Address:
5140 E GLENN ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM09060
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09060 REV1

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The location of RTU AC-9 shown on Drawing S1 does not match with location shown on Mechanical Drawing M1. Verify and make revisions as needed.
2. Provide Structural Calculations for Roof Framing members supporting the new RTU’s per Section 1601.1 of International Building Code 2018.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2022 NGARCIA3 OUT TO CUSTOMER Completed